To remove the laminated steel bar, remove the
two
upper securing bolls from
the
compound transformer
and
lift
the
barlrom
the transformer. The
add~ion
01
shim thickness will raise the no-load voltage and,
conversely, the removal
01
shim thickness will lower the no-load voltage.
Varying shim thickness by
.001
inch (0.025 mm) will change the no-load voltage
by
4 to 6 Volts. (Shim
material should be non-conductive; that
is,
tt
should be transparent
or
colored stationary store materiaL)